Installation Requirements - Page 7
1.3 Location Of Boiler
In siting the combination boiler, the following limitations,
MUST be observed:
a) The position selected for installation should be
within the building, unless otherwise protected by a
suitable enclosure. It must allow adequate space for
installation, servicing and air circulation around the
appliance.
b) This position MUST also allow the chosen flue
termination to be made correctly. The boiler must be
installed on a flat vertical wall which is capable of
supporting the weight of the appliance and any
ancillary equipment.
The appliance may be installed on a combustible wall,
subject to the requirements of the Local Authorities and
Building Regulations.
IMPORTANT NOTICE: If the combination boiler is to
be fitted in a timber framed building it should be fitted in
accordance with the British Gas publication 'Guide for
Gas Installations in Timber Frame Housing'. (Reference
DM2). If in doubt advice must be sought from the Local
Gas Region.
The combination boiler may be installed in any room or
internal space, although particular attention is drawn to
the requirements of the current I.E.E. Wiring
Regulations, and in Scotland, the electrical provisions of
the Building Regulations applicable in Scotland, with
respect to the installation of the combination boiler in a
room or internal space containing a bath or shower.
Where a room-sealed appliance is installed in a room
containing a bath or shower, any electrical switch or
appliance control, utilising mains electricity should be so
situated that it cannot be touched by a person using the
bath or shower.
A compartment used to enclose the combination boiler
MUST be designed and constructed specifically for this
purpose. An existing cupboard, or compartment, may
be used provided it is modified accordingly. See Section
1.4 'Air Supply'.
Where installation will be in an unusual location, special
procedures may be necessary. BS 6798 gives detailed
guidance on this aspect.
Clearances around the Appliance - Fig. 4.
Side Clearance: For operation and servicing, 25 mm
each side.
Top Clearance: A minimum of 160 mm, but 300 mm is
preferred to allow removal of the central heating
expansion vessel, without removing the appliance from
the wall, if replacement is required.
Bottom Clearance: A bottom clearance of 220 mm is
required between the appliance and any surface.
Frontal Clearance: A minimum of 500 mm is required in
front of the appliance for access during servicing, the
front clearance can be reduced providing the door/cover
can be removed to expose the entire case front.
1.4 Air Supply
Detailed recommendations for air supply are given in BS
5440:2. The following notes are intended for general
guidance: It is not necessary to have a purpose provided
air vent in the room or internal space in which the
combination boiler is installed. If the combination boiler is
to be installed in a cupboard or compartment, permanent
air vents are required (for cooling purposes) in the
cupboard/compartment, at both high and low levels. The
air vents must either communicate with a room/or be
direct to outside air.
Table 1. Air Supply
1.5 Flue Systems & Terminal Location
The standard horizontal flue system is suitable for
installations up to 1092 mm, measured from the centre
line of the boiler outlet to the outside face of the wall. The
wall liner enclosed will accommodate thicknesses of 400
mm and can be cut to a minimum length of 76 mm.
One metre flue extension kits are available to extend
horizontal flues to a maximum length of 3078 mm.
90° In-line elbow kits and 135° In-line Bend kits are also
available for more flexible siting. Horizontal flues can be
set at 45° angles to the combination boiler, through 360°,
to the miniature terminal on the outside of the building.
A Concentric Vertical flue system is available which
when used in conjunction with One metre flue
extension kits is suitable flue heights up to 3 metres to
terminate through a roof.
A Twin tube Vertical flue system is also available for
flue heights up to 8025 mm when used in conjunction
with one metre twin tube extension kits.