INSTRUCTIONS PERTAINING TO THE INSTALLER
To facilitate measurement of the combustion efciency and improve the cleanliness of the production products,
the chimney sweep function can be activated by proceeding as described below:
1) Press the (2-3) together until the pointer appears on the display alongside the symbol (about 3
seconds but no more than 6 seconds). In these conditions, the boiler operates at the maximum heat output
in central heating mode.
2) Press either of the buttons to exit the function
020429_0200
Figure 18
To ensure the boiler operates at peak efciency, the following checks must be performed every year:
Check on the appearance and tightness of the gas and combustion circuit gaskets;
Check on the condition and position of the ignition and ame sensing electrodes (see section 16);
Check on the condition of the burner and its xing to the aluminium ange;
Check for any dirt in the combustion chamber. Use a vacuum-cleaner for this cleaning operation;
Check that the gas valve is calibrated correctly (see section 13);
Check that there is no dirt in the siphon;
Check on the central heating system pressure;
Check on the central heating expansion vessel pressure.
18. ACTIVATING THE CHIMNEY SWEEP FUNCTION
19. ANNUAL SERVICE